TECHNOLOGY:
|
TRUE ON LINE Double Conversion
|
CLASSIFICATION CODE:
|
VFI - SS - 111
|
POWER RANGE:
|
6-10 kVA
|
PHASE CONFIGURATION:
|
1:1
|
SOFTWARE:
|
ViewPower
|
APPLICATIONS:
Servers, Workstations, Lighting, Lab equipment, Security systems, Automation and control systems
Model | CORE 6K | CORE 10K |
Power | 6000 VA 6000 W |
10000 VA 10000 W |
No. of phases IN : OUT | 1:1 |
Input |
Nominal voltage | 208 / 220 / 230 / 240 Vac |
Voltage range | -30% ÷ +30% @ 100% ≥ load > 80% -40% ÷ +30% @ 80% ≥ load > 70% -48% ÷ +30% @ 70% ≥ load > 60% -52% ÷ +30% @ 70% ≥ load > 0% |
Frequency | 50 / 60 Hz |
Frequency range | -20% ÷ +20% |
THDi | <3% |
Input power factor | ≥0,99 |
Output |
Nominal voltage | 208 / 220 / 230 / 240 Vac | ||||
Output power factor | 1,0 | ||||
Voltage regulation static/dynamic | ±1% / ±3% | ||||
Frequency | 50 / 60 ±0,05 Hz | ||||
Overload capacity inverter | 110% - 10min, 130% - 1 min., > 130% - 1 sek. | ||||
Efficiency on-line mode | >95% | ||||
Efficiency eco Mode | 99% | ||||
Controlled socet groups | Yes | ||||
Creast factor | 3:1 |
Batteries |
Amount of internal batteries | - | ||||
Cold start | Yes | ||||
Connector for external batteries | Yes | ||||
Charging time | 4 hours up to 90% capacity |
Weight and dimensions |
Weight and dimensions of UPS (W x D x H) [mm] |
438 x 665 x 88 (2U) | 438 x 665 x 88 (2U) |
17,0 kg | 20,0 kg | |
Weight and dimensions of battery module (W x D x H) [mm] |
438 x 630 x 133 (3U) | 438 x 630 x 133 (3U) |
63,0 kg | 63,0 kg |
Communications |
Working indicator | LCD panel + sound alarm |
Communications | Standard: RS232, USB, TVSS, SNMP Slot, REPO Optional: AS-400 (drycontact), LAN/SNMP, RS485 ModbusRTU |
Enviromental |
Noise level | <50 dB | ||
Operating temperature for UPS | 0°C ÷ 45°C | ||
Recommended operating temperature for UPS | 15°C ÷ 25°C | ||
Storage Temperature | -25°C ÷ 55°C | ||
Humidity | 0 ÷ 95% (without condensing) |
Standards |
Standards | EN 62040-2:2005, EN 62040-2:2006 | ||
Safety | IEC62040-1-1, CE, 62040-3 :2001 |
Options |
- SNMP card - Enviromental sensor (EMD) - Maintenance bypass - REPO |
- Additional battery module - Rail Kit 19'' - AS-400 (Relay Card) - RS485 card (ModbusRTU) |
Do you need help?
Tel: +48 58 556 13 13
E-mail: info@comex.com.pl
Filing a Complaint
Tel: +48 58 556 13 13
E-mail: info@comex.com.pl