Model |
PRM 6K |
Capacity [VA / W] |
6000 / 5400 |
No. Of phases IN : OUT |
1:1 |
Voltage |
200 / 208 / 220 / 230 / 240 VAC |
Voltage range |
- 30% ÷ + 25% @ ≥70% load |
- 48% ÷ + 25% @ <70% load |
Frequency |
50/60 Hz |
Frequency range |
-20% ÷ +20% |
Input power factor |
≥0,99 |
Voltage |
208 / 220 / 230 / 240 VAC |
Voltage regulation static/dynamic |
±1% / ±3% |
Frequency |
50/60 ± 0,05 Hz |
Frequency conversion |
Yes, 50Hz / 60Hz |
Overload capacity (1) |
112% - continuous, 145% - 2min., 150% - 30sec., |
Efficiency Online (2) /Eco mode |
> 95% / 99% |
Output sockets |
IEC320-C13 x 4 IEC320-C19 x 2 |
Terminal boards |
Yes, with maintenance manual Bypass switch |
Crest factor |
3:1 |
Battery type |
Maintenance free, sealed VRLA AGM |
Battery startup |
Yes |
External battery connector |
Yes(4) |
Recharging time |
4 hours up to 90% capacity |
Dimensions of UPS [mm] (W x D x H) |
438 x 698 x 129 mm (3U) |
Weight of UPS with internal batteries |
46 kg |
Operation mode indicators |
LCD screen, sound alarm |
Communication |
RS-232, Dry Contact in/out (5), USB, SNMP slot, REPO |
Noise level (6) |
<50 db (A) |
Operating temperature for UPS |
0 °C ÷ 40 °C |
Recommended. operating temperature for UPS and batteries |
15 °C ÷ 25 °C |
Storage temperature |
- 25 °C ÷ 55 °C |
Humidity |
0 ÷ 95 % (non condensing) |
Standards |
CE, EN62040-2:2006 (EMC), EN62040-1:2008 (LVD) |
- SNMP card - Monitoring and shutdown software, WinPower - AS 400 Card
|
- 19” Rack-mount kit - Remote status panel - Environmental sensor (EMD) - REPO |
(1) for cosφ=0.8 (2) for cosφ=0.9 and 100% load (3) autonomy times for pf=0.7 ± 10% can vary depending on battery type, operating temp etc. (4) up to 4 battery modules (5) for PRM 1-3kVA
(6) max value, noise level can be lower due to automatic fan regulation.
In the publication are given standard parameters of our models. Due to continuous product improvement, we reserve the right to change parameters without prior notice.