TECHNOLOGY:
|
True On-Line, Double Conversion
|
|
CLASSIFICATION:
|
VFI-SS-111 (EN 62040-3)
|
|
POWER RANGE:
|
30 - 300 kVA
|
|
No. OF PHASES:
|
3:3
|
APPLICATIONS:
Large computer networks, data processing centres, clusters, medical and industrial equipment, tele-information systems, automation and control systems
| Model | BW300 | |||
| Capacity kVA | 30 - 300 kW/kVA | |||
| Number of phases IN:OUT | 3:3 | ||
| Capacity of power module | 30 kW/kVA | ||
| Hotswap power module | Yes | ||
| Possibility of configuration | 10, 15, 20, 25 or 30 kW power module | ||
| Input |
| Voltage | 380 / 400 / 415 VAC |
| Voltage range | 305 – 478 Vac for load ≥70% 208 – 478 Vac for load <70% |
| Frequency | 50 / 60 Hz |
| Frequency range | -20% ÷ +20 % |
| THDi | <3% |
| Input power factor | ≥ 0,99 |
| Output |
| Voltage | 380 / 400 / 415 VAC |
| Voltage regulation static/dynamic | ±1% / ±2% |
| Frequency | 50 / 60 ± 0,05 Hz |
| Overload capacity | 110% - 60 min., 125% - 10 min., 150% - 60 s, >150% - 200 ms |
| Efficiency | >96% |
| Eco Mode efficiency | 99% |
| Crest factor | 3:1 |
| Batteries |
| Type | Maintenance free, sealed VRLA AGM |
| Quantity | 32/36/40 pcs |
| Cold start | yes |
| Charging | 4 – 8 hours up to 90% of capacity, in accordance with DIN 41773 |
| Weight and dimensions |
| Weight and dimensions of cabinet (WxDxH) |
BW STS | |||
| 600 mm x 1100 mm x 2000 mm | ||||
| 275 kg | ||||
| Weight and dimensions of power module (WxDxH) |
BW PM 30 | |||
| 440 mm x 650 mm x 135 mm (3U) | ||||
| 34,5 kg | ||||
| Communications |
| Operation mode indicators | LCD touch screen, LED indicators, sound alarm |
| Communication | RS-232, USB, Dry Contact, SNMP slot, REPO, parallel work connector, Automatic diagnostic and error logs. Logs error > 2600 |
| Environmental |
| Noise Level depending the load and temp. |
< 60 dB (A) | ||
| Operating temperature for UPS | 0 °C ÷ 40 °C | ||
| Recom. operating temperature for UPS and batteries |
15 °C ÷ 25 °C | ||
| Storage temperature | -20°C ÷ 40°C | ||
| Humidity | 0 ÷ 95 % (without condensation) | ||
| Standards |
| Standards | CE, EN62040-1:2008, EN62040-2:2006, | ||
| Options |
| - SNMP Web - Environmental sensor (EMD) - REPO |
- External battery cabinets - External Maintenance Bypass - 30kVA Power modules |