TECHNOLOGY:
|
True On-Line, Double Conversion
|
CLASSIFICATION CODE:
|
VFI-SS-111 (EN 62040-3)
|
POWER RANGE:
|
10 - 100 kVA
|
PHASE CONFIGURATION:
|
3:3
|
APPLICATIONS:
Servers, Workstations, Building infrastructure equipment, Laboratory equipment, Tele information systems, Automation and control systems
Basic set of PKX 10 kVA / 10 kW UPS with batteries
Model | PKX 10K |
Power | 10 kVA / kW |
No. Of phases IN : OUT | 3:3 |
Input |
Voltage | 380 / 400 / 415 Vac |
Voltage range | 190 – 520 Vac |
Frequency | 50 / 60 Hz ± 20% |
THDi | <3% |
Input power factor | ≥0,99 |
Output |
Power factor | 1,0 |
Voltage | 380 / 400 / 415 Vac |
Voltage regulation static/dynamic | ±1% / ±3% |
Frequency | 50 / 60Hz ± 0,1 Hz |
Overload | <110% - 30 min., 130% - 5 min.,150% - 10 sec, >150% - 200 ms. |
Efficiency in On-Line mode/Eco mode | 95% / 98 % |
Crest factor | 3:1 |
Batteries |
Type | Maintenence-free, AGM type VRLA |
Battery range number | 32-40 psc |
Charging current | 4 A |
Charging time | 3 – 4 hours up to 90% of capacity (configurable) |
Weight and dimensions |
Dimensions of UPS [mm] (W x D x H) | 418 x 635 x 132 (3U) |
Weight of UPS without batteries | 20 kg |
Communication |
Working indicator | LCD screen + LED, sound alarm |
Communication | SNMP slot, USB, EPO , RS232 |
Parallel | Possibly to work in parallel up to 10 units |
Enviromental conditions |
Noise level (depends how many modules) | <55 dB | ||
Operating temperature | 0°C ÷ 40°C | ||
Recommended operating temperature | 15 °C ÷ 25 °C | ||
Storage temperature | -20°C ÷ 40°C | ||
Humidity | 0 ÷ 95% (without condensing) |
Standards |
EMC | EN62040-2 | ||
Standards | CE, EN62040-1, EN 61000-4-1, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-2-2 |
Options |
- SNMP card - Uninterruptible external maintenance bypass |
- External batteries in battery packs - Environmental sensor (EMD) |