TECHNOLOGY:
|
Line Interactive
|
CLASSIFICATION CODE:
|
VI - SS - 111 (zg. z PN-EN 62040-3)
|
POWER RANGE:
|
3 kVA
|
PHASE CONFIGURATION:
|
1:1
|
SOFTWARE:
|
ViewPower
|
Model | WINTER 3K |
Rating | 2700 W / 3000 VA |
Phases In : Out | 1:1 |
Input |
Mains voltage range | 162 ÷ 290 VAC | ||
Frequency | 50 / 60 Hz (autosensing) |
Output |
Nominal voltage | 208 / 220 / 230 / 240 VAC |
Power factor | 0,9 |
Voltage regulation (battery mode) | ±1,5% |
Nominal frequency (battery mode) | 50 / 60 ± 1 Hz |
Transfer time | 1,5÷6 ms |
Efficiency in normal mode | 97% |
Crest factor | 3:1 |
Output receptacles | IEC 320 C13 (10A) – 8 pcs IEC 320 C19 (16A) – 1 pc. |
Batteries |
Cold start | yes | ||
Batteries quantity | 6 pcs | ||
Charging time | 3 – 8 hours to 90% of capacity | ||
Charging | According to DIN 41773, 3-stage charging extends battery service life. | ||
Backup time with internal batteries - 100% load - 75% load - 50% load |
4 min 7 min 12 min |
Weight and dimensions |
UPS dimensions (SxGxW) | 438 mm x 630 mm x 88 mm (2U) 29,3 kg |
Communications |
User interfaces | Rotatable LCD panel, sound alarm |
Communications | RS232, USB, TVSS, EPO Optional: Dry Contact, SNMP |
Environmental |
Audible Noise | <42 dB | ||
Operating temperature | 0°C ÷ 40°C | ||
Recommended temperature | 15°C ÷ 25°C | ||
Storage temperature | -20°C ÷ 40°C | ||
Humidity | 0 ÷ 95% (non-condensing) |
Standards |
EMC markings | EN 62040-2:2005, EN 62040-2:2006 | ||
Safety markings | IEC62040-1-1, CE, 62040-3 :2001 |
Options |
- SNMP card - AS-400 card - Environmental sensor (EMD) |
- External battery modules (EBM) - 19' Rack mount kit - Emergency Power Off button (REPO) |
Do you need help?
Tel: +48 58 556 13 13
E-mail: info@comex.com.pl
Filing a Complaint
Tel: +48 58 556 13 13
E-mail: info@comex.com.pl