Model |
HS205 |
Power |
150 kW/kVA |
200 kW/kVA |
Nominal voltage |
380 / 400 / 415 VAC |
Voltage range |
-43% ÷ +25% |
Nominal frequency |
50/60 Hz |
Frequency range |
-20% ÷ +20% |
THDi |
<3% |
Input power factor |
≥ 0,99 |
Nominal voltage |
380 / 400 / 415 VAC |
Power factor |
1.0 |
Voltage regulation static/dynamic |
±1% / ±2% |
Nominal frequency |
50/60 ± 0,05 Hz |
Inverter overloads |
110% - 10 min., 125% - 1 min., 150% - 5 s, >150% - 200 ms |
Bypass overloads |
110% - const, 125% - 5 min., 150%-400$ - 1 sec., >400% - 200 ms |
Short circuit capability |
340% of nominal current by 200 ms |
Efficiency On Line mode |
>96% |
Efficiency Eco Mode |
99% |
Crest factor |
5:1 |
Cold start |
available |
Batteries quantity |
Regulable, nominal 480Vdc |
Charging time |
Regulable, 3 – 8 hours to 90% of capacity |
Charging methods |
According to DIN 41773 |
Dimensions (W x D x H) and weight |
650 mm x 960 mm x 1600 mm |
305 kg |
350 kg |
Indicators |
Touchable colourfull panel 10’’, LED indicators, independent LCD panel on each power module, sound alarm |
Communications |
RS232, RS485, MODBUS RTU/ASCII, USB, Dry Contact, SNMP, REPO, parallel ports. |
Noise level |
<65 dB@load 100%, <62 dB@load. 50% |
Permissible operating temperature |
0 °C ÷ 40 °C |
Recommended operating temperature |
15 °C ÷ 25 °C |
Storage temperature |
-20°C ÷ 40°C |
Humidity |
0 ÷ 95% (without condensation) |
Resistance to interference |
EN 62040-2:2005, EN 62040-2:2006 |
Safety |
IEC62040-1-1, CE, 62040-3 :2001 |
- SNMP adapter - Uninterrupted external Bypass |
- Additional batteries in modules or on open scaffoldings - Battery charging voltage compensation kit |
W publikacji podano parametry standardowych modeli. W związku ze stałym udoskonalaniem produktu zastrzega się możliwość zmian parametrów bez uprzedniego informowania.