Model |
NGS 40K |
Power |
40 kVA / 40 kW |
No. Of phases IN : OUT |
3:3 |
Voltage |
380 / 400 / 415 VAC |
Voltage range |
-43% ÷ +20% |
Frequency |
50 / 60 Hz |
Frequency range |
-20% ÷ +20% |
THDi |
<3% |
Input power factor |
≥0,99 |
Voltage |
380 / 400 / 415 VAC |
Power factor |
1,0 |
Voltage regulation static/dynamic |
±1% / ±2% |
Frequency |
50 / 60 ± 0,05 Hz |
Overload capacity inverter |
110% - 60 min., 125% - 10 min., 150% - 60 s, >150% - 300 ms |
Overload capacity bypass |
125% - continuous, 130% - 10 min., 150% - 1 min., >150% - 300 ms |
Shot-circuit resistance |
340% value of nominal current for 200 ms |
Efficiency in On-Line mode |
>96% |
Efficiency in Eco Mode |
99% |
Crest factor |
3:1 |
Cold start |
Yes (option) |
Amount of batteries in 1 string (external batteries) |
36-44 pcs x 12V |
Internal batteries |
2 x 40 x 12 Ah or 4 x 36 x 7/9Ah |
Charging time |
3 – 8 hours up to 90% of capacity (configurable) |
Dimensions of UPS [mm] (W x D x H) |
500 x 840 x 1400 |
Weight of UPS without internal batteries |
140 kg |
Working indicator |
LCD + indicators LED, sound alarm |
Communication |
RS232, RS485, USB , DryContact Option: SNMP, REPO, parallel work
|
Noise level (depends how many modules) |
<58 dB @ load. 100%, <52 dB @ load. 50% |
Operating temperature for UPS |
0 °C ÷ 40 °C |
Recommended. operating temperature for UPS |
15 °C ÷ 25 °C |
Storage temperature |
-20°C ÷ 40°C |
Humidity |
0 ÷ 95 % (without condensing) |
Standards |
EN 62040-2:2005, EN 62040-2:2006 |
Safety |
IEC62040-1-1, CE, 62040-3 :2001 |
- Uninterruptible external maintenance bypass - SNMP card - Environmental sensor (EMD)
|
- Battery Cold Start - Parallel card |
In the publication are given standard parameters of our models. Due to continuous product improvement, we reserve the right to change parameters without prior notice.