TECHNOLOGY:
|
True On-Line, Double Conversion
|
CLASSIFICATION CODE:
|
VFI - SS - 111
|
POWER RANGE:
|
30 - 120 kVA
|
PHASE CONFIGURATION:
|
3:3
|
SOFTWARE:
|
W opcji
|
APPLICATIONS:
Large computer networks, Data Processing Centres, facilities and equipment, laboratory equipment, telecommunication, automation and control systems
Model | NHS |
Power | 30kW / 30kVA - 120kW / 120kVA |
No. of phases IN:OUT | 3:3 |
Input |
Nominal voltage | 380 / 400 / 415 VAC |
Voltage range | -40% ÷ +25% |
Frequency | 50/60 Hz |
Frequency range | -20% ÷ +20% |
THDi | <2,5% |
Input power factor | ≥ 0,99 |
Output |
Nominal voltage | 380 / 400 / 415 VAC |
Power factor | 1,0 |
Static / dynamic voltage regulation | ±0,5% / ±2% |
Nominal frequency | 50/60 ± 0,01 % |
Inverter overload resistance | 110% - 60 min., 125% - 10 min., 150% - 60 sek., >150% - 200msek. |
Short-circuit resistance | 340% of the nominal current for 200 ms |
Efficiency in On-Line mode | >96% |
Eco Mode efficiency | 99% |
Creast factor | 3:1 |
Batteries |
Type | Sealed, maintenance-free AGM type VRLA |
Cold start | yes |
Length of the battery string | 36 – 44 psc. batteries 12V |
Charging time | 3 - 8 hours to 90% capacity (configurable) |
Charging cycle | According to DIN 41773 with automatic charging switch According to the criterion of charging current and voltage with time control, the option of temperature compensation of the charging voltage |
Dimensions and weight |
UPS housing dimensions and weight (W x D x H) | 600 x 980 x 1400 mm |
259 kg |
Signaling and communication ports |
Work status indicator | Touch LCD display, LED indicators, audible alarm |
Communication | RS232, RS485, MODBUS RTU / ASCII, Dry Contact, SNMP, REPO, parallel operation interface, interface with the genset |
Environmental conditions |
Noise level (depending on the number of power modules) | <55 dB | ||
Operating temperature | 0 °C ÷ 40 °C | ||
Recommended working temperature | 15 °C ÷ 25 °C | ||
Storage temperature | -20°C ÷ 40°C | ||
Humidity | 0 ÷ 95% (without condensation) |
Standards |
Resistance to interference | EN 62040-2 :2006 C3, EN 61000-2-2 :2002, EN 61000-4-2 :2009, EN 61000-4-3 :2006 +A1 :2008 +A2 :2010, EN 61000-4-4 :2004 +A1 :2010, EN 61000-4-5 :2006, EN 61000-4-6 :2009, EN 61000-4- 8 :2010, EN 61000-4-11 :2004 | ||
Safety | CE, EN 62040-1 :2008, EN 60950-1:2006, IEC 60417 |
Optional equipment |
- SNMP card, - Charging voltage compensation system, - Environmental conditions sensor (EMD) |
- Batteries on a rack or battery modules - Service Uninterruptible Bypass External |
Do you need help?
Tel: +48 58 556 13 13
E-mail: info@comex.com.pl
Filing a Complaint
Tel: +48 58 556 13 13
E-mail: info@comex.com.pl