TECHNOLOGY:
|
True On-Line, Double Conversion
|
CLASSIFICATION CODE:
|
VFI - SS - 111
|
POWER RANGE:
|
10 - 40 kVA
|
PHASE CONFIGURATION:
|
3:3
|
SOFTWARE:
|
ClientMate
|
APPLICATIONS:
Computers network, Data processing centers, Industrial equipment, Clusters, Tele information systems, Automation and control systems
Model | NGS 10 | NGS 15 | NGS 20 | NGS 30 | NGS 40 |
Power | 10 kVA / 10 kW | 15 kVA / 15 kW | 20 kVA / 20 kW | 30 kVA / 27 kW | 40 kVA / 40 kW |
No. of phases: IN : OUT | 3:3 |
Input |
Nominal voltage | 380 / 400 / 415 VAC |
Voltage range (adjustable) | -43% ÷ +20% |
Frequency | 50 / 60 Hz |
Frequency range | -20% ÷ +20% |
THDi | <3% |
Input power factor | ≥0,99 |
Output |
Nominal voltage | 380 / 400 / 415 VAC | ||||
Power factor | 1,0 | 0,9 | 1,0 | ||
Static / dynamic voltage regulation | ±1% / ±2% | ||||
Nominal frequency | 50 / 60 ± 0,05 Hz | ||||
Overload capacity inverter | 110% - 60 min., 125% - 10 min., 150% - 60 sec | ||||
Overload capacity bypass | 125% - continuous, 130% - 10 min., 150% - 1 min | ||||
Shot-circuit resistance | 340% value of nominal current for 200 ms | ||||
Efficiency in On-Line mode | >96% | ||||
Efficiency in Eco Mode | 99% | ||||
Crest factor | 3:1 |
Batteries |
Cold start | Yes (option) |
Amount of batteries in 1 string | 36-44 psc. of batteries 12V |
Charging time | 3 – 8 hours up to 90% of capacity (configurable) |
Charging cycle | According to DIN 41773 with automatic disconnection of charging according to the criterion of current and voltage, with time control, option of temperature compensation of the charging voltage |
Weight and dimensions |
Dimensions and weight (W x D x H) | 250 x 840 x 715 | 350 x 737 x 1335 | 500 x 840 x 1400 | ||
without internal batteries | 51,5 kg | 88,0 kg | 140,0 kg |
Communication |
Working indicators | LCD + indicators LED, sound alarm |
Communication | RS232, RS485 As option: MODBUS RTU/ASCII, USB, Dry Contact, SNMP, REPO, złącza pracy równoległej |
Environmental |
Noise level | <58 dB @ load 100%, <52 dB @ load. 50% |
Operating temperature for UPS | 0 °C ÷ 40 °C |
Recommended operating temperature for UPS | 15 °C ÷ 25 °C |
Storage temperature | -20°C ÷ 40°C |
Humidity | 0 ÷ 95% (without condensing) |
Certification |
Standards | EN 62040-2:2005, EN 62040-2:2006 | ||||
Safety | IEC62040-1-1, CE, 62040-3 :2001 |
Options |
- Uninterruptible external maintenance bypass - SNMP card - Environmental sensor (EMD) |
- Battery Cold Start - Parallel card |