TECHNOLOGY:
|
TRUE ON LINE Double Conversion
|
CLASSIFICATION:
|
VFI-SS-111 (EN 62040-3)
|
POWER RANGE:
|
60 ÷ 120 kVA
|
No. OF PHASES:
|
3:3
|
SOFTWARE: | upsSmartView |
APPLICATION:
Large computer networks, Data processing centers, Industrial facilities and equipment, Laboratory equipment, Telecommunication, Automation and control systems
HIGH AVAILABILITY
Super wide input range - Input voltage range: 138~485Vac (linear derating at 138~ 304Vac and 40%~100% load, and no derating at 304~485Vac), input frequency range: 40~70Hz, 50/60Hz, power grid system which is self-adaptive, suitable for harsh power grid environment, greatly reduce battery discharge times, extend battery life, and easier to match with the operation of small capacity generator.
Double input - Double input design, support independent bypass, improve the availability of the bypass.
High power factor - The output power factor 1.0, 11% higher than the carrying capacity of traditional products with PF=0.9.
Adjustable cell number - Support ±15~22 (30~44) cells, which can be flexibly configured. The cell cost can be reduced by fewer cells in the early stage, and the maintenance cost can be saved by more cells in the later stage (the battery can be double eliminated in case of failure, and the maintenance is convenient on the basis of meeting the discharge time). The lithium battery system can be customized.
Cold start function - In the case of no mains, UPS can be started directly with the battery to meet emergency needs.
Zero switching - Pure online dual transform design: when the mains is unstable, the time for switching to UPS is zero to effectively ensure the security and reliability of load operation.
Starting delay after power recovery - The restarting time delay after power recovery can be set to reduce the impact on the power grid or the
generator.
Frequency conversion mode - Support frequency conversion mode of 50Hz input /60Hz output and 60Hz input /50Hz output to meet the special needs of the users.
RICH OPTIONAL ACCESSORIES
Standard: RS232, USB, RS485, RJ45, input and output dry contact, parallel interface, LBS interface, EPO and battery temperature compensation interface.
Optional: SNMP card, WIFI card, GPRS card, parallel cable, LBS cable, battery temperature sensor, EMD environment detector and SMS alarm.
HIGH INTELLECTUALITY
Intelligent management - It supports various communication interfaces such as RS232, USB, RS485, RJ45, SNMP card, WIFI card, GPRS card and 4G card to monitor the running status of UPS locally or by the network. After configuring WIFI card, GPRS card and 4G card, UPS can be monitored through mobile APP in real time.
Battery management - Intelligent battery management, automatic floating charge control and charger sleep control can improve the reliability of charger and increase the battery life. Regular battery self-test can be carried out through monitoring.
ENERGY CONSERVATION AND ENVIRONMENT PROTECTION
Active power factor correction - Adopting digital controlled active power factor correction (PFC) technology, the input power factor is up to more than 0.99, avoiding pollution to the grid environment, achieving energy saving and reducing the cost of system investment.
Overall efficiency - System efficiency increased to 96% and energy saving rate doubled.
ECO mode - When the power grid is in good condition, the working efficiency is up to 99% with high efficiency and energy saving after the ECO mode is started. In ECO working mode, a 120 kVA UPS full-load work can save 9500 EUR (calculated by 0,3 EUR per kWh) in electric charge for one year.).
Model | Frame 60 | Frame 80 | Frame 100 | Frame 120 |
Rated capacity | 60 kVA / 60 kW | 80 kVA / 80 kW | 100 kVA / 100 kW | 120 kVA / 120 kW |
Input |
Input wiring | Three-phase, five line (3 Φ + N + PE) |
Rated voltage | 380Vac/400Vac/415Vac (line voltage) |
Voltage range | 304 Vac ~ 485 Vac (no downgrading) 138 Vac ~ 304 Vac (linear downgrading at 40% ~ 100% load) |
Frequency range | 40 ~ 70 Hz |
Power factor | ≥ 0.99@100% resistive load, ≥ 0.97@50% resistive load |
Total harmonic of input current (THDi) | ≤ 3%@100% resistive load, ≤ 5%@50% resistive load |
Bypass input voltage range | 380 Vac: -20% ~ +15% (upper limit +10%/+15%/+20%/+25% settable) 400 Vac: -20% ~ +15% (upper limit +10%/+15%/+20% settable) 415 Vac: -20% ~ +10% (upper limit +10%/+15% settable) (lower limit -60%/-50%/-40%/-30%/-20%/-10% settable) |
Bypass frequency range | ±5 Hz (±1 Hz/±2 Hz/±3 Hz/±4 Hz/±5 Hz/±6 Hz settable) |
ECO voltage range | ±10% (±5%/±6%/±7%/±8%/±9%/±10% settable) |
ECO frequency range | ±2 Hz (±1 Hz/±2 Hz/±3 Hz settable) |
Output |
Output wiring | Three-phase five line (3 Φ + N + PE) |
Rated voltage | 380 Vac/400 Vac/415 Vac ±1% (line voltage) |
Output frequency | Mains mode: tracking bypass input in synchronous state; Battery mode or frequency conversion mode or beyond the frequency tracking range: 50 Hz/60 Hz ± 0.1% |
Power factor | 1 |
Output waveform distortion (THDv) | ≤ 1% (linear load); ≤ 4% (non-linear load) |
Output voltage imbalance | ≤ 3% |
Output voltage phase deviation | ≤ 1° |
Crest factor | 3:1 |
Switching time | Mains mode - battery mode: 0 ms; Inverter mode - bypass mode (synchronous switching): 0 ms; Inverter mode -ECO mode (synchronous switching): 0 ms; |
Inverter overload capability | 105% < load 110%, switching to bypass in 60 minutes; 110% < load 125%, switching to bypass in 10 minutes; 125% < load 150%, switching to bypass in 1 minute; Load > 150%, switching to bypass in 0.2 seconds |
Battery |
Battery type | Lead-acid battery | |||
Battery voltage | 360 Vdc ~ 528 Vdc (30 ~ 44 pcs selectable, 40 pcs by default) | |||
Equalizing charge voltage | 2.31 V/Cell (settable to 2.30 ~ 2.40 V/Cell) | |||
Floating charge voltage | 2.25 V/Cell (settable to 2.23 ~ 2.27 V/Cell) | |||
Maximum charging current | 24 A | 36 A | ||
Charging temperature compensation | -3 mV/℃ for T ≥ 25℃ ( -1 ~ -8 mV /℃ settable),0 mV per℃ for T < 25 ℃ |
System |
Display | 5.0 inch touch color screen |
Efficiency | 96% in online mode, 99% in ECO mode |
Protections | Output short circuit protection, output overload protection, over-temperature protection, low battery protection, output over/under-voltage protection, fan fault protection, etc |
Max. number of parallel connections | 4 |
Environmental |
Operating temperature | 0 ~ 40℃ |
Storage temperature | -25 ~ 55℃ (without battery) |
Humidity | 0 ~ 95% (non-condensing) |
Altitude | ≤ 1000 m; for above 1000 m, downgrading 1% for each additional 100 m; Max. 5000 m; 0 ~ 5000 m settable |
IP rating | IP 20 |
Noise | ≤ 65 dB (at 1 m) |
Communication |
Communication interface | Standard: RS232, RS485, USB, NET, EPO, LBS, parallel, input/output dry contacts, dual smart card slot, 1-way battery temperature sampling interface; Optional: SNMP card, GPRS card, Wi-Fi card, battery temperature sensor, parallel cable, etc |
Physical |
Wiring mode | Bottom cable entry | |||
Dimensions (W × D × H) (mm) | 360 × 850 × 950 | 360 × 850 × 1200 | 440 × 850 × 1200 | |
Packed dimensions (W x D x H) (mm) | 450 × 940 × 1120 | 450 × 940 × 1370 | 530 × 940 × 1370 | |
Net weight (kg) | 130,5 | 156,0 | 198,0 | |
Gross weight (kg) | 145,0 | 172,0 | 218,5 |