TECHNOLOGY:
|
True ON-LINE Double Conversion
|
CLASSIFICATION:
|
VFI-SS-111
|
POWER RANGE:
|
300 - 1200 kW
|
No. OF PHASES:
|
3:3
|
APPLICATION:
Large computer networks, Data processing centers, Industrial facilities and equipment, Laboratory equipment, Telecommunication, Automation and control systems
Model | BM | ||||||
Power | 300kVA/300kW | 400kVA/400kW | 500kVA/500kW | 600kVA/600kW | 800kVA/800kW | 1000kVA/1000kW | 1200kVA/1200kW |
No. of phases IN : OUT | 3:3 |
Input |
Nominal Voltage | 380 / 400 / 415 VAC | |||
Voltage range | -40% ÷ +25% | |||
Frequency | 50 / 60 Hz | |||
Frequency range | -10% ÷ +10 % | |||
THDi | <3% | |||
Input power factor | ≥0,99 |
Output |
Power factor | 1,0 |
Nominal voltage | 380 / 400 / 415 VAC |
Static / dynamic voltage regulation | ±1% / ±3% |
Nominal frequency | 50 / 60 Hz ± 0,1 Hz |
Inverter overload resistance | 130% - 10 min., 150% - 60s, >150% - 200ms |
Efficiency in On-Line mode | 97% |
Efficiency in Eco mode | 99% |
Battery |
No. of batteries in string | 32 – 44 psc. batteries 12Vㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤㅤ38 – 48 psc. batteries 12V | ||||||
Charging current | 25 - 100A | 25 - 200A | |||||
Charging time | 3-8 hours to 90% capacity (configurable) | ||||||
Charging cycle | According to DIN 41773 with automatic shutdown of charging according to the criterion of current and voltage, with time control. |
Dimensions and weight |
Dimensions (W x D x H) | 1000 x 900 x 1950 mm | 1400 x 900 x 1950 mm | 1900 x 900 x 1950 mm | 3000 x 900 x 1950 mm | |||
Weight | 750 kg | 1100 kg | 1300 kg | 2400 kg |
Signaling and communication ports |
Work status indicator | Touch display, LED indicators, audible alarm |
Standard communication | RS232, RS485, MODBUS, USB, Dry Contact, SNMP (option), REPO, Parallel slots, interface for gensets |
Environmental conditions |
Noise level | <75 dB @ load. 100%, <65 dB @ load. 50% | ||
Permissible operating temperature | 0 °C ÷ 40 °C | ||
Recommended working temperature | 15 °C ÷ 25 °C | ||
Storage temperature | -20°C ÷ 40°C | ||
Humidity | 0 ÷ 95% (without condensation) |
Standards |
Resistance to interference | EN 62040-2:2005, EN 62040-2:2006 | |||
Safety | IEC62040-1-1, CE, 62040-3 :2001 |
Optional equipment |
- SNMP card |
- Batteries in rack or in battery modules, - Parallel card |