TECHNOLOGY:
|
TRUE ON LINE Double Conversion
|
|
CLASSIFICATION CODE:
|
VFI-SS-111 (zg. z PN-EN 62040-3)
|
|
POWER RANGE:
|
10 ÷ 40 kVA
|
|
PHASE CONFIGURATION:
|
1:1, 3:1, 3:3, 1:3
|
APPLICATIONS:
Computer networks, Servers, Rack cabinets 19", Laboratory apparatus, Telecommunications, Automation and control systems
| UPS PS - 19'' rack installation with battery modules | UPS PS - free-standing, Tower with battery modules |
|
|
|
| Model | PS 10K | PS 20K | PS 30K | PS 40K |
| Power | 10 kVA / 10 kW | 20 kVA / 20 kW | 30 kVA / 30 kW | 40 kVA / 40 kW |
| No. of phases IN : OUT | 1:1, 3:1, 3:3, 1:3 | 3:3 |
| Input |
| Nominal voltage [L-N] | [L-L] | 220 / 230 / 240 VAC | 380 / 400 / 415 VAC |
| Voltage range [L-N] [L-L] |
100 ÷ 160 VAC linearly for load. 50% - 100%, 160 ÷ 300 VAC for load 100% 174 ÷ 278 VAC linearly for load 50% - 100%, 278 ÷ 522 VAC for load 100% |
| Frequency | 50 / 60 Hz |
| Frequency range | 45 ÷ 65 Hz |
| THDi | <3% |
| Input power factor | ≥0,99 |
| Output |
| Nominal voltage [L-N] | [L-L] | 220 / 230 / 240 VAC | 380 / 400 / 415 VAC | ||||
| Power factor | 1,0 | ||||
| Static/dynamic voltage regulation | ±1% / ±3% | ||||
| Nominal frequency | 50 / 60 ± 0,1 Hz | ||||
| Overload resistance | 105% bez limitu, 125% - 10 min., 150% - 30 s., >150% - 500 ms | ||||
| Efficiency in On-line mode | >96% | ||||
| Efficiency in ECO mode | 98% | ||||
| Creast factor | 3:1 | ||||
| Batteries |
| Number of batteries in 1 string | 32 - 40 pcs. of batteries 12V | ||||
| Charging current | 1 - 13 A | ||||
| Charging time | 3 - 8 hours up to 90% capacity (configurable) | ||||
| Charging cycle | According to DIN 41773 with automatic charge deactivation according to current and voltage criteria, with time control, temperature compensation option for charging voltage | ||||
| Dimensions and weight |
| Dimensions UPS W x D x H [mm] | 440 x 680 x 132 (3U) | 440 x 750 x 132 (3U) | |||
| Weight of 1 UPS module | 25 kg | 32 kg | 36 kg | 38 kg | |
| Dimensions of 1 battery module W x D x H [mm] (20 bat.) 1 | 440 x 780 x 132 (3U) | ||||
| Weight of 1 battery module (20 bats) 2 | 65 kg | ||||
| Signalling and communication ports |
| Operating status indicator | LCD, audible alarm |
| Communication | USB, RS232, EPO, SNMP |
| Environmental conditions |
| Noise level (dependent on number of power modules) | <65 dB @ load 100% |
| Permissible operating temperature | 0°C ÷ 40°C |
| Recommended operating temperature | 15°C ÷ 25°C |
| Storage temperature | -20°C ÷ 40°C |
| Humidity | 0 ÷ 95% (non-condensing) |
| Standards |
| Resistance to interference | EN 62040-2:2018, EN 61000-3-2:2019, EN 61000-3-3:2013+A1:2019 |
| Safety | EN 62040-1:2019, EN 62040-1-2:2003, 62040-3:2001, CE |
| Optional equipment |
| - SNMP adapter - Uninterruptible External Bypass, Service |
- 19" rack-mounted or rack-mounted battery modules - Remote Fire Protection Switch - REPO |
1The UPS must have a minimum of 2 battery modules. Each of these modules is respectively the positive and negative half of the UPS battery chain, together they occupy 6U.
2Each UPS must have a minimum of 2 battery modules.