| Model |
HS505 |
| Power |
450 kW/kVA |
500 kW/kVA |
| Nominal voltage |
380 / 400 / 415 VAC |
| Voltage range |
-43% ÷ +25% |
| Nominal frequency |
50/60 Hz |
| Frequency range |
-20% ÷ +20% |
| THDi |
<3% |
| Input power factor |
≥ 0,99 |
| Nominal voltage |
380 / 400 / 415 VAC |
| Power factor |
1.0 |
| Voltage regulation static/dynamic |
±1% / ±2% |
| Nominal frequency |
50/60 ± 0,05 Hz |
| Inverter overloads |
110% - 60 min., 125% - 10 min., 150% - 60 s, >150% - 1s |
| Bypass overloads |
110% - const, 125% - 5 min., 150% - 1 min., >150% - 1 s |
| Short circuit capability |
340% of nominal current by 200 ms |
| Efficiency On Line mode |
>96% |
| Efficiency Eco Mode |
99% |
| Crest factor |
5:1 |
| Cold start |
available |
| Batteries quantity |
Regulable, nominal 480Vdc |
| Charging time |
Regulable, 3 – 8 hours to 90% of capacity |
| Charging methods |
According to DIN 41773 |
| Dimensions (W x D x H) and weight |
1300 mm x 1100 mm x 2000 mm |
| 855kg |
900 kg |
| Indicators |
Touchable colourfull panel 10,4’’, LED indicators, independent LCD panel on each power module, sound alarm |
| Communications |
RS232, RS485, MODBUS RTU/ASCII, USB, Dry Contact, SNMP, REPO, parallel ports. |
| Noise level |
<65 dB@load 100%, <62 dB@load. 50% |
| Permissible operating temperature |
0 °C ÷ 40 °C |
| Recommended operating temperature |
15 °C ÷ 25 °C |
| Storage temperature |
-20°C ÷ 40°C |
| Humidity |
0 ÷ 95% (without condensation) |
| Resistance to interference |
EN 62040-2:2005, EN 62040-2:2006 |
| Safety |
IEC62040-1-1, CE, 62040-3 :2001 |
- SNMP adapter - Uninterrupted external Bypass |
- Additional batteries in modules or on open scaffoldings - Battery charging voltage compensation kit |
W publikacji podano parametry standardowych modeli. W związku ze stałym udoskonalaniem produktu zastrzega się możliwość zmian parametrów bez uprzedniego informowania.